Reactor Physics & Kinetics · C-RX-012

Power Coefficient — Reactivity per 1 % Power and Its Integral, the Power Defect

Reactivity per 1 % power, its integral the power defect, and why it is more negative at end of cycle.

Definition

The power coefficient (αP) is the change in core reactivity per 1 % change in reactor power (relative to rated), αP = dρ/dP, in pcm/%power (some references write it as %Δk/k per %power, e.g. −0.012 = −12 pcm/%); because fuel temperature, moderator temperature (density) and voids all change with power, it is a composite coefficient: the individual coefficients weighted by how fast each temperature changes with power.

In short, it is the rate of reactivity change with power, equal to the moderator and fuel temperature coefficients weighted by the temperature change per unit power, and it is designed to be negative over the whole power operating range.

Principle and mechanism

Coefficient × temperature change per unit power

For a PWR, ignoring the void and pressure terms:

  • αP = MTC·(dTM/dP) + FTC·(dTF/dP)
  • MTC, FTC: temperature coefficients in pcm/K (or pcm/°F)
  • dTM/dP: change in average moderator temperature per unit power (K/%), set by the variable-Tavg operating program
  • dTF/dP: change in average fuel temperature per unit power (K/%), set by the fuel-rod thermal resistance (pellet conductivity and gap conductance)

Because each term is a coefficient times a rate, the power coefficient is not "MTC + FTC". That sum is the isothermal temperature coefficient, ITC = MTC + FTC. This note focuses on tying the two coefficients to a single variable, power.

The derivative is the power coefficient; the integral is the power defect

Integrating the power coefficient from 0 % to P gives the power defect (PD):

  • PD(P) = ∫₀ᴾ αP dP′ (in pcm)

The coefficient is the slope; the defect is the accumulated total. Raising power inserts negative reactivity equal to the power defect, which must be offset by withdrawing control rods or diluting boron. Conversely, when power falls and the fuel and moderator cool, the same amount comes back as positive reactivity feedback.

What it means in a plant

Beginning versus end of cycle

Values read from the figures in a US NRC training manual (a Westinghouse-type training example core):

ItemBOLEOL
Total power coefficient (0 → 100 %)−13.5 → −11.9 pcm/%−22.0 → −20.8 pcm/%
100 % power defectabout −1,210 pcmabout −2,130 pcm
Doppler shareabout −1,180 pcmabout −1,030 pcm
Moderator share (total − Doppler, estimated by subtraction)about −30 pcmabout −1,100 pcm
Fuel temperature rise (0 → 100 %)about 1,000 °Fabout 800 °F
Left: power coefficient versus power, BOL from −13.5 to −11.9 and EOL from −22.0 to −20.8 pcm per %, with the 80 to 100 % area worth about −416 pcm. Right: its integral, the power defect, reaching −1,254 pcm at BOL and −2,110 pcm at EOL, with reference points at about −1,210 and −2,130. Below: bars splitting the 100 % defect into Doppler −1,180 plus moderator about −30 at BOL and Doppler −1,030 plus moderator about −1,100 at EOL, a vessel-head image for compensation by rods and boron, and the formula alpha P = MTC·dTM/dP + FTC·dTF/dP
Power coefficient and power defect for a Westinghouse-type training example core (curves read from the NRC HRTD Westinghouse Technology Manual 2.1; the defect curve is the calculated integral). The EOL defect is about 1.7 times the BOL value, and the increase is mostly the moderator (MTC) contribution.

Three points matter:

  1. EOL is more negative. The source attributes this "primarily to the change in the moderator temperature coefficient": with boron diluted, the MTC grows to around −30 to −45 pcm/°F.
  2. The Doppler share actually shrinks a little at EOL. Pellet swelling and cladding creep close the gap, so the fuel temperature rise at the same power is smaller (dTF/dP decreases).
  3. At BOL the power defect is almost all Doppler; at EOL Doppler and moderator share it roughly equally.

Integrating the digitized power-coefficient curve directly gives a 100 % defect of −1,254 pcm at BOL and −2,110 pcm at EOL, within a few percent of the source's power-defect figure; the EOL defect is about 1.7 times the BOL value. The curve shape also shows that the coefficient is slightly less negative at higher power, because Doppler broadening saturates at high temperature and the FTC magnitude falls. The power defect is therefore nearly a straight line, but strictly it is slightly convex upward.

Self-regulation and load changes

A negative power coefficient is what makes the reactor hold its own power (self-regulation). An example in the same manual shows this well. With an MTC of −20 pcm/°F and a Doppler power coefficient of −10 pcm/%, reducing turbine load from 60 % to 50 % without moving control rods gives:

  • Less heat removed from the primary side, so Tavg rises → negative reactivity
  • Power falls, so fuel temperature drops → positive reactivity
  • A new equilibrium where a Tavg rise of 5 °F (−100 pcm) balances a 10 % power reduction (+100 pcm)

The equilibrium condition is αM·ΔTavg + αD,P·ΔP = 0. In real operation, the variable-Tavg program requires Tavg to rise with power, so the power defect inserted when power is raised is compensated with rods or boron. That adjustment is made to hold Tavg on its programmed value, not to make the reactor follow power.

In load-follow operation, reactivity equal to the power defect has to be added and removed with every power swing. At EOL the defect is larger while the boron concentration is low, so offsetting the same reactivity with boron takes more dilution water and more time. Reliance on control rods grows, and so does the burden of managing the axial power distribution and xenon oscillations.

Stability and safety analysis

  • A positive power coefficient is unstable: a power perturbation increases reactivity, which increases power further. At low power the Chernobyl RBMK had a positive power coefficient because of its large positive void coefficient (INSAG-7).
  • Too negative is also a burden: the positive reactivity returned on a power reduction or trip is large, and recriticality margins are worse in cooldown events such as a main steam line break.
  • Safety analysis therefore uses both ends: the least negative (BOC) value for heat-up and reactivity-insertion events, the most negative (EOC) value for cooldown events.
  • So that the core stays subcritical against the positive reactivity released as power and temperature fall after shutdown, the control-bank insertion limit (minimum rod height) rises with power.

Worked examples

  • Example 1: FTC = ITC − MTC = −12 − (−10) = −2 pcm/K. αP = (−10)(2) + (−2)(10) = −40 pcm/%power. This is a training value larger than real PWR values (−12 to −22 pcm/%).
  • Example 2: FTC = −6 − (−5) = −1 pcm/K. αP = (−5)(1) + (−1)(5) = −10 pcm/%power, with moderator and fuel contributing −5 each.
  • Example 3: from 0 → 100 %, fuel 300 → 800 °C and moderator 300 → 320 °C.
    • (a) Δρ = (−2.0)(500) + (−5.0)(20) = −1,000 − 100 = −1,100 pcm
    • (b) αP = −1,100/100 = −11 pcm/%power (average over 0–100 %)
    • (c) With boron fixed, +1,100 pcm is needed → 1,100/10 = 110 steps of rod withdrawal
    • (d) With rods fixed, 1,100/10 = 110 ppm of dilution
    • The Doppler share is 91 %, similar to the BOC make-up.

Regulatory and design criteria

The criteria below are examples from the United States (US NRC) and the IAEA.

  • For example, US NRC 10 CFR 50 Appendix A, GDC 11 (Reactor inherent protection): in the power operating range, the net effect of the prompt inherent nuclear feedback characteristics shall tend to compensate for a rapid increase in reactivity. A negative power coefficient is the operating indicator of this requirement.
  • NUREG-0800 SRP 4.3 (Nuclear design): reviews calculation methods and uncertainties for reactivity coefficients, including the power coefficient, and the coefficient ranges used in transient analysis.
  • Technical specifications (STS NUREG-1431 Rev. 5): there is no LCO on the power coefficient itself. It is managed indirectly through the MTC (LCO 3.1.3), shutdown margin (3.1.1) and control-bank insertion limits (3.1.6); the numbers are in each unit's COLR.
  • IAEA: SSR-2/1 (Rev. 1, 2016) core design requirements; SSG-52 (2019) core design guide.

Easily confused pairs

Power coefficientPower defectIsothermal temperature coefficient (ITC)Temperature defect
Definitiondρ/dP∫αP dPMTC + FTC∫ITC dT
Unitpcm/%pcmpcm/Kpcm
VariablePowerPower intervalUniform temperatureTemperature interval (cold → hot zero power)
UseSelf-regulation, transient analysisCompensation, shutdown marginHZP measurementCooldown shutdown margin

The power coefficient and power defect are a derivative and its integral, and so are the ITC and the temperature defect. In calculations, simply checking the units catches most mix-ups: a sum of coefficients in pcm/K is the ITC, not the power coefficient, and a defect in pcm is not a coefficient in pcm/%.

Key points at a glance

  1. Definition: αP = dρ/dP, reactivity change per 1 % power (pcm/%power).
  2. Make-up: αP = MTC·dTM/dP + FTC·dTF/dP (PWR, voids ignored).
  3. Power defect: PD = ∫₀ᴾ αP dP, the reactivity accumulated from 0 → 100 % (pcm).
  4. Compensation: power ↑ → rod withdrawal or boron dilution; power ↓ → +ρ feedback as temperatures fall → control-bank insertion limits preserve the shutdown margin.
  5. Cycle dependence: more negative at EOC (mainly MTC); the Doppler share falls slightly as the gap closes.
  6. Representative values (training example): BOL about −12 pcm/%, defect about −1,200 pcm; EOL about −21 pcm/%, about −2,100 pcm.
  7. Self-regulation: a negative power coefficient lets Tavg and power settle at a new equilibrium after a load change.
  8. Safety analysis: BOC (least negative) → heat-up and reactivity events; EOC (most negative) → cooldown events.
  9. Criteria (examples): US NRC GDC 11 (reactor inherent protection), SRP 4.3; IAEA SSR-2/1.
Sketch: power defect in pcm plotted downward against power, a solid BOL line to about −1,200 and a dashed EOL line to about −2,100 at 100 %, the gap labelled added defect approximately moderator share, a slope triangle ΔPD/ΔP approximately alpha P, and the formulas PD(P) = integral of alpha P dP and alpha P = MTC·dT_M/dP + FTC·dT_F/dP
Sketch: the power defect as a straight-line approximation, whose slope is the power coefficient.